Generator Rental Charts
Visit our formulas and charts for general rentals and cable.

Generator Assurance
Need to be sure a generator rental is available to you?

Event Services
Need generator rental solution for your next event?

Need quiet generators?

ELECTRICAL FORMULAS

To Obtain

SINGLE PHASE
(Alternating Current)

THREE PHASE
(Alternating Current)

Kilowatts

V x l x pf

1000

1.732 x V x l x pf

1000

kV•A

V x l

1000

1.732 x V x l

1000

Amperes
(kW known)
kW x 1000

V x pf

kW x 1000

1.732 x V x pf

Amperes
(motor hp known)
hp x 0.746

V x pf x Efficiency
hp x 0.746

1.732 x V x pf x Efficiency
Amperes
(kV•A known)
kV•A x 1000

V
kV•A x 1000

1.732 x V
Horsepower
(kW unknown)
kW

0.746 x Efficiency
(Generator)
kW

0.746 x Efficiency
(Generator)
Horsepower
(generator efficiency unknown)
kW

0.746 x 0.93
kW

0.746 x 0.93
kW input
(motor hp known)
hp x 0.746

Efficiency
(Motor)
hp x 0.746

Efficiency
(Motor)
kW input (motor efficiency? unknown) hp x 0.85 hp x 0.85